Type MC
CCA Cable

600V | Premium Building Wire

The Copperweld Metal-Clad (MC) Cable Advantage

Copperweld® Metal-Clad (MC) Cable is a cost-stable, energy-efficient alternative to wiring methods such as conductors in conduit and cable tray.

Copperweld® MC Cable is manufactured to UL standards and complies with the National Electrical Code (NEC). When sized appropriately according to the NEC, it has the lowest voltage drop of the three branch circuit conductor material alternatives. Disincentivizing pilferage and theft, it offers thieves only a small fraction of the scrap value of single-metal copper scrap.

Product overview

Copper-Clad Aluminum (CCA) Conductor — Drawn from a copper-clad aluminum rod, with the copper metallurgically bonded to an AA 8000 series aluminum core, where oxygen-free copper forms a minimum of 10 percent of the cross-sectional area of a solid conductor or each strand of a stranded conductor.

Application Standards — UL 1569

Conductors — For wire sizes 12-10, solid annealed THHN Copper-Clad Aluminum with solid Copper Clad Aluminum ground.  For 8 AWG sizes and larger, stranded annealed THHN Copper-Clad Aluminum with solid Copper-Clad Aluminum ground.

Conductor Insulation — Type THHN or THWN-2 with a heat-stabilized Nylon jacket rated for 75°C in wet locations and 90°C in dry locations.

Grounding Conductor — For NM-B 12-10 AWG sizes: ground will be 12-10 AWG, solid, annealed conductor. For NM-B 8 AWG sizes and larger: ground will be 8 AWG, solid, annealed.

Metal-Clad Jacket — Lightweight steel or aluminum interlocking armor

Identification, applications and usage

Copperweld® Copper-Clad Aluminum Type MC (Metal-Clad cable) is referenced by Article 330 of the National Electrical Code.  OSHA safety listed: UL E523379. ETL listing: 5021266.

Identified for use with Wiring Devices, Splice Connectors and Equipment Terminals Rated for Cu, Cu/Al and CO/ALR. Copperweld® MC Cable is NRTL listed for safety. It is made with ASTM B-566 Copper-Clad Aluminum bare Copperweld® wire, which carries its own component listing, RU DVVU2. Copperweld MC conductors are suitable to terminate on 15 and 20 ampere rated wiring devices (receptacles and snap switches) marked ‘copper only’ or ‘CO/ALR’.  For termination on devices rated 30 amperes or greater, the termination must be marked ‘CU/AL’ or equivalent.  Please consult UL Product IQ guide information RTRT and WJQR if further confirmation is required. Copperweld® MC Cable may be pigtailed to single-metal copper wire in dry or wet locations with terminals and connectors specified for such use. Copperweld® MC Cable should not be terminated with single-metal Aluminum wire without the application of an oxide inhibitor or a terminal or connector specifically listed for such use. Copperweld® ASTM B-566 Copper-Clad Aluminum wire is not dissimilar to copper, brass or zinc plated steel.

  • Commercial buildings, large places of public assembly (auditoriums, churches, museums, gymnasiums, conference rooms, restaurants, etc.), industrial manufacturing and processing plants
  • Secondary feeders in industrial and commercial distribution systems; supplying electricity to station auxiliaries in power stations
  • May be used exposed or concealed, in approved raceways or as open run
  • ETL Listed conforming to UL 1569
  • Conforms to Article 330 of NEC approved wiring method
  • Cable tray rated, 600 Volt, 90°C rated
  • Handles branch, feeder and service circuits (Articles 230-243)
  • For use in theaters (Article 520), motion picture and TV studios (Article 530), and assembly spaces with over 100 people (Article 518)
  • For use in Class I, Div. 2, Class II, Div. 2 and Class III, Div. 1 hazardous locations

Copperweld MC Cable Product Offering

12 AWG

Replaces: 14 AWG Solid Copper

12/2-G

12/3-G

12/4-G

Conductor Construction:

Solid

Solid

Solid

Sheath Material:

Aluminum

Aluminum

Aluminum

Ground Wire Size:

12 AWG

12 AWG

12 AWG

THHN Insulation Thickness (PVC):

0.015

0.015

0.015

THHN Jacket Thickness (Nylon):

0.004

0.004

0.004

Allowable Amperage @ 60° C

15

15

15

Allowable Amperage @ 75° C*

20

20

20

Allowable Amperage @ 90° C

25

25

25

Outside Diameter (in)

0.495

0.530

0.565

Nom. Weight per lbs/1000 ft

83

100

118

Standard Packaging

250' Coil, 1000' Wood Reel

250' Coil, 1000' Wood Reel

250' Coil, 1000' Wood Reel

*
Ampacity of THHN conductors are based on NFPA 70 (NEC) Table 310.16 for a temperature rating of the conductors of 75°C. See 110.14 (C), 240.4(D), 310.15(B) and 334.80 for other limitations where applicable. 

10 AWG

Replaces: 12 AWG Solid Copper

10/2-G

10/3-G

10/4-G

Conductor Construction:

Solid

Solid

Solid

Sheath Material:

Aluminum

Aluminum

Aluminum

Ground Wire Size:

10 AWG

10 AWG

10 AWG

THHN Insulation Thickness (PVC):

0.020

0.020

0.020

THHN Jacket Thickness (Nylon):

0.005

0.005

0.005

Allowable Amperage @ 60° C

25

25

25

Allowable Amperage @ 75° C

30

30

30

Allowable Amperage @ 90° C

35

35

35

Outside Diameter (in)

0.560

0.600

0.645

Nom. Weight per lbs/1000 ft

111

136

162

Standard Packaging

250' Coil, 1000' Wood Reel

250' Coil, 1000' Wood Reel

250' Coil, 1000' Wood Reel

*
Ampacity of THHN conductors are based on NFPA 70 (NEC) Table 310.16 for a temperature rating of the conductors of 75°C. See 110.14 (C), 240.4(D), 310.15(B) and 334.80 for other limitations where applicable. 

8 AWG

Replaces: 10 AWG Solid Copper

8/2-G

8/3-G

Conductor Construction:

7 Strands

7 Strands

Sheath Material:

Aluminum

Aluminum

Ground Wire Size:

8 AWG

8 AWG

THHN Insulation Thickness (PVC):

0.030

0.030

THHN Jacket Thickness (Nylon):

0.005

0.005

Allowable Amperage @ 60° C

35

35

Allowable Amperage @ 75° C

40

40

Allowable Amperage @ 90° C

45

45

Outside Diameter (in)

0.710

0.770

Nom. Weight per lbs/1000 ft

171

210

Standard Packaging

250' Coil, 1000' Wood Reel

250' Coil, 1000' Wood Reel

*
Ampacity of THHN conductors are based on NFPA 70 (NEC) Table 310.16 for a temperature rating of the conductors of 75°C. See 110.14 (C), 240.4(D), 310.15(B) and 334.80 for other limitations where applicable. 

Copperweld Building Wire Benefits

Reduces Theft Incentive

CCA offers a fraction of the scrap value of copper building wire.

Energy Efficient

When sized per Code, CCA delivers improved energy efficiency over alternatives.

Easy to Install

CCA is lightweight, flexible, and terminates to standard torquing values.

Code Compliant

NEC compliant for 600 Volt residential branch circuit conductors since 1971.

Safety Tested

Listed for safety for use in general electrical wiring and branch circuits.

Proven Performance

CCA has 50 years of safe performance history in standard circuits.

Quotes and orders

Copperweld's friendly sales team is ready to fill your order or help you select products to deliver the performance you need.

Stay connected

Follow us on your favorite social platforms:

Get updates

Sign up for Copperweld news to learn about the latest industry updates, events, product releases, videos and technical documents.

Thank you! Your submission has been received!
Oops! Something went wrong. Make sure you filled out ALL the required fields and completed the reCaptcha challenge.